Duct Size Chart: CFM to Duct Diameter & Size Guide

A 12 in round duct for 400 CFM. A 10 in duct carries only 382 CFM, so 400 CFM needs the next size up: 550 CFM of capacity, a 10×12 in rectangular equivalent, and air moving at 509 FPM. Enter your airflow to size your duct.

847

Duct size chart — CFM to duct diameter

A duct is sized from the air it must carry: the capacity is the area times the design velocity, and the duct you pick is the smallest one whose capacity covers the airflow. This calculator works out the round diameter, the rectangular equivalent and the air velocity for any airflow, with the full CFM-to-size table at the 700 FPM residential design velocity.

How much air the duct must carry, in cubic feet per minute. The default is 400 CFM.

12 in round duct — 550 CFM capacity12 in round duct — 550 CFM capacity12 in round duct for 400 CFM: 550 CFM capacity at 700 FPM, rectangular equivalent 10×12 in, air velocity 509 FPM. Capacity = round duct area ÷ 144 × 700 FPM; velocity = CFM ÷ duct area in sq ft. The smallest duct whose capacity covers the airflow wins.

Round duct: 12 in

Capacity at 700 FPM: 550 CFM

Rectangular equivalent: 10×12 in

Air velocity: 509 FPM

Max CFM of a 10 in duct: 382 CFM

Max CFM of an 8 in duct: 244 CFM

Max CFM of a 14 in duct: 748 CFM

Duct size for 250 CFM: 9 in

Duct size for 500 CFM: 12 in

Branch: 100 CFM: 6 in, 6×8 in, 509 FPM

Branch: 200 CFM: 8 in, 8×8 in, 573 FPM

Branch: 300 CFM: 9 in, 8×10 in, 679 FPM

Branch: 600 CFM: 14 in, 12×14 in, 561 FPM

Branch: 1,000 CFM: 18 in, 16×18 in, 566 FPM

Branch: 1,500 CFM: 20 in, 18×20 in, 688 FPM

12 in round duct for 400 CFM. Capacity 550 CFM at 700 FPM, rectangular equivalent 10×12 in, air velocity 509 FPM.

100 CFM: 6 in, 6×8 in, 509 FPM.

200 CFM: 8 in, 8×8 in, 573 FPM.

300 CFM: 9 in, 8×10 in, 679 FPM.

600 CFM: 14 in, 12×14 in, 561 FPM.

1,000 CFM: 18 in, 16×18 in, 566 FPM.

1,500 CFM: 20 in, 18×20 in, 688 FPM.

Reverse: a 10 in duct carries 382 CFM at 700 FPM; an 8 in duct carries 244 CFM; a 14 in duct carries 748 CFM; 250 CFM needs a 9 in duct (309 CFM capacity); 500 CFM needs a 12 in duct (550 CFM capacity).

How duct size is worked out

A duct is sized from the airflow it must carry. The design basis here is 700 feet per minute (FPM), the usual residential design velocity for supply ducts. A round duct’s area is π times half the diameter squared, in square inches. Its CFM capacity is the area divided by 144 — to get square feet — times 700 FPM. The duct you pick is the smallest one whose capacity is at least the airflow you need. The rectangular equivalent is the listed standard size whose area is at least the round area, and the air velocity at your airflow is the CFM divided by the duct area in square feet.

At the default — 400 CFM — a 10 in duct carries only 382 CFM, so it is too small. A 12 in duct is 113.10 sq in, so it carries 550 CFM, which covers the 400 CFM with room to spare. The duct is a 12 in round duct, its rectangular equivalent is 10×12 in, and the air moves at 400 ÷ 0.7854 = 509 FPM.

Round duct (in)Area (sq in)Max CFM at 700 FPMRectangular equivalent
519.63956×6 in
628.271376×8 in
738.481878×8 in
850.272448×8 in
963.623098×10 in
1078.5438210×10 in
12113.1055010×12 in
14153.9474812×14 in
16201.0697714×16 in
18254.471,23716×18 in
20314.161,52718×20 in
CaseDuctCapacityRectangularVelocity
Default (400 CFM)12 in550 CFM10×12 in509 FPM
100 CFM6 in137 CFM6×8 in509 FPM
200 CFM8 in244 CFM8×8 in573 FPM
300 CFM9 in309 CFM8×10 in679 FPM
600 CFM14 in748 CFM12×14 in561 FPM
1,000 CFM18 in1,237 CFM16×18 in566 FPM
1,500 CFM20 in1,527 CFM18×20 in688 FPM

The worked example, line by line

Setup: airflow 400 CFM, design velocity 700 FPM.

Line 1 — the 10 in duct. Area = π × 5² = 78.54 sq in; capacity = 78.54 ÷ 144 × 700 = 382 CFM — too small for 400 CFM.

Line 2 — the 12 in duct. Area = π × 6² = 113.10 sq in; capacity = 113.10 ÷ 144 × 700 = 550 CFM — the smallest size that covers 400 CFM.

Line 3 — the rectangular equivalent. 10 × 12 = 120 sq in, which is at least the round area of 113.10 sq in, so the equivalent is 10×12 in.

Line 4 — the air velocity. 400 ÷ (113.10 ÷ 144) = 400 ÷ 0.7854 = 509 FPM.

Reverse: a 10 in duct carries 382 CFM at 700 FPM; an 8 in duct carries 244 CFM; a 14 in duct carries 748 CFM; 250 CFM needs a 9 in duct (309 CFM capacity); 500 CFM needs a 12 in duct (550 CFM capacity).

Every branch, checked

100 CFM: a 5 in duct carries only 95 CFM, so the smallest size that covers it is a 6 in duct (137 CFM), rectangular 6×8 in, velocity 509 FPM.

200 CFM: a 7 in duct carries 187 CFM, so the smallest size that covers it is an 8 in duct (244 CFM), rectangular 8×8 in, velocity 573 FPM.

300 CFM: an 8 in duct carries 244 CFM, so the smallest size that covers it is a 9 in duct (309 CFM), rectangular 8×10 in, velocity 679 FPM — close to the 700 FPM design velocity.

600 CFM: a 12 in duct carries 550 CFM, so the smallest size that covers it is a 14 in duct (748 CFM), rectangular 12×14 in, velocity 561 FPM.

1,000 CFM: a 16 in duct carries 977 CFM, so the smallest size that covers it is an 18 in duct (1,237 CFM), rectangular 16×18 in, velocity 566 FPM.

1,500 CFM: an 18 in duct carries 1,237 CFM, so the smallest size that covers it is a 20 in duct (1,527 CFM), rectangular 18×20 in, velocity 688 FPM — the biggest size on the chart.

Reverse — the other way round: a 10 in duct carries 382 CFM; an 8 in duct carries 244 CFM; a 14 in duct carries 748 CFM; 250 CFM needs a 9 in duct; 500 CFM needs a 12 in duct.

What the defaults assume

The model assumes the airflow you enter and the 700 FPM residential design velocity, and it picks the smallest table diameter whose capacity covers the airflow. It assumes a single round duct for the whole airflow and the listed standard rectangular sizes, and it leaves out fittings, dampers, long runs and static pressure — a real design checks the whole system, not one duct. Airflows above 1,527 CFM are outside the chart and need an HVAC pro. Rounding convention: CFM capacities are rounded to the nearest whole CFM, velocities to the nearest whole FPM, and all figures are computed from unrounded values, rounded only for display.

Output · formula · meaning

OutputFormulaWhat it means
Round ductsmallest diameter whose capacity ≥ CFM12 in.
Capacity at 700 FPMround area ÷ 144 × 700550 CFM.
Rectangular equivalentlisted size whose area ≥ round area10×12 in.
Air velocityCFM ÷ duct area in sq ft509 FPM.
Max CFM of a 10 in ductarea ÷ 144 × 700382 CFM.
Max CFM of an 8 in ductarea ÷ 144 × 700244 CFM.
Max CFM of a 14 in ductarea ÷ 144 × 700748 CFM.
Duct size for 250 CFMsmallest capacity ≥ 2509 in (309 CFM capacity).
Duct size for 500 CFMsmallest capacity ≥ 50012 in (550 CFM capacity).
100 CFMsame model, 100 CFM6 in, 6×8 in, 509 FPM, capacity 137 CFM.
200 CFMsame model, 200 CFM8 in, 8×8 in, 573 FPM, capacity 244 CFM.
300 CFMsame model, 300 CFM9 in, 8×10 in, 679 FPM, capacity 309 CFM.
600 CFMsame model, 600 CFM14 in, 12×14 in, 561 FPM, capacity 748 CFM.
1,000 CFMsame model, 1,000 CFM18 in, 16×18 in, 566 FPM, capacity 1,237 CFM.
1,500 CFMsame model, 1,500 CFM20 in, 18×20 in, 688 FPM, capacity 1,527 CFM.

Who uses this

  • The homeowner adding a room: they learn 400 CFM needs a 12 in duct with a 10×12 in rectangular equivalent — so they know the size to ask for, and they check the 100 CFM case at 6 in before sizing the branch.
  • The HVAC installer sizing a run: they learn a 10 in duct carries only 382 CFM — so they know the 400 CFM run needs the next size up, and they check the 600 CFM case at 14 in before cutting the duct.
  • The DIYer converting round to rectangular: they learn a 12 in round duct is a 10×12 in rectangular duct — so they know the soffit size, and they check the 18 in row at 16×18 in before framing the chase.
  • The contractor checking a big system: they learn 1,500 CFM needs a 20 in duct — so they know the chart’s top size, and they check the 1,527 CFM maximum before promising a bigger run.

Accuracy & limitations

The math is exact for the numbers you enter: the capacity is the round area divided by 144 times 700 FPM, the duct is the smallest size whose capacity covers the airflow, and the velocity is the CFM divided by the duct area in square feet. What the model cannot do is design your system for you: check the airflow, because a 100 CFM branch and a 1,000 CFM trunk need very different ducts. It assumes one duct for the whole airflow at 700 FPM and leaves out fittings, dampers, long runs and static pressure. For the furnace behind the ducts, see furnace size calculator; for the filter the air passes through, see air filter size chart.

Cite this calculatorBright Side Kit. “Duct Size Chart: CFM to Duct Diameter & Size Guide.” brightoolbox.com, 2026. Method: design velocity 700 FPM (residential design basis); round duct area = π × (diameter ÷ 2)² sq in; CFM capacity = area ÷ 144 × 700, rounded to the nearest whole CFM; pick the smallest diameter whose capacity is ≥ the entered CFM; rectangular equivalent = the listed standard size whose area is ≥ the round area; velocity = CFM ÷ (area ÷ 144), rounded to the nearest whole FPM. Table: 5 in → 95 CFM → 6×6 in; 6 in → 137 CFM → 6×8 in; 7 in → 187 CFM → 8×8 in; 8 in → 244 CFM → 8×8 in; 9 in → 309 CFM → 8×10 in; 10 in → 382 CFM → 10×10 in; 12 in → 550 CFM → 10×12 in; 14 in → 748 CFM → 12×14 in; 16 in → 977 CFM → 14×16 in; 18 in → 1,237 CFM → 16×18 in; 20 in → 1,527 CFM → 18×20 in. Default: 400 CFM → 12 in round duct (550 CFM capacity), rectangular 10×12 in, velocity 509 FPM. Branches: 100 CFM → 6 in, 6×8 in, 509 FPM; 200 CFM → 8 in, 8×8 in, 573 FPM; 300 CFM → 9 in, 8×10 in, 679 FPM; 600 CFM → 14 in, 12×14 in, 561 FPM; 1,000 CFM → 18 in, 16×18 in, 566 FPM; 1,500 CFM → 20 in, 18×20 in, 688 FPM. Reverses: max CFM of a 10 in duct 382 CFM; 8 in 244 CFM; 14 in 748 CFM; 250 CFM → 9 in (309 CFM); 500 CFM → 12 in (550 CFM). Bright Side Kit. "Duct Size Chart: CFM to Duct Diameter & Size Guide." https://brightoolbox.com/duct-size-chart/ Accessed October 25, 2026.
Embed this calculator

Paste this into any web page to embed the live calculator. The “Powered by Bright Side Kit” link below it must stay intact.

Frequently asked questions

What size duct do I need for 400 CFM?

A 12 in round duct. A 12 in duct carries 550 CFM at the 700 FPM residential design velocity, so it is the smallest size that covers 400 CFM. Its rectangular equivalent is 10×12 in, and the air moves at 509 FPM in it.

How do you calculate duct size from CFM?

Divide the airflow by the design velocity, then pick the smallest duct that covers it. At 700 FPM, a duct’s CFM capacity is its area in square inches ÷ 144 × 700. A 10 in duct is 78.54 sq in, so it carries 382 CFM; a 12 in duct is 113.10 sq in, so it carries 550 CFM. Pick the smallest diameter whose capacity is at least the airflow.

What size duct for 100 CFM?

A 6 in round duct. A 6 in duct carries 137 CFM at 700 FPM, so it covers 100 CFM with room to spare, and the air moves at 509 FPM. A 5 in duct carries only 95 CFM, so it is too small.

What is the rectangular equivalent of a round duct?

The rectangular size with at least the same area. A 12 in round duct is 113.10 sq in, so its equivalent is 10×12 in (120 sq in). A 10 in round duct is 78.54 sq in, so its equivalent is 10×10 in (100 sq in). The chart above gives the equivalent for every size.

What happens if the CFM is above the table?

The chart tops out at 20 in, which carries 1,527 CFM. Above that the calculator says so and points to an HVAC pro, instead of guessing a size. A duct that big needs a proper design, not a chart lookup.

Why is the design velocity 700 FPM?

700 feet per minute is the usual residential design velocity for supply ducts. Faster air is noisier and costs more fan power; slower air needs bigger ducts. The whole chart is built on 700 FPM, so every capacity here is the airflow at that velocity.

How fast is the air in my duct?

CFM divided by the duct area in square feet. At 400 CFM in a 12 in duct the velocity is 400 ÷ 0.7854 = 509 FPM. At 300 CFM in a 9 in duct it is 679 FPM, close to the 700 FPM design velocity.