AWG Wire Gauge Chart

Every American Wire Gauge size from hair-thin 40 AWG to service-entrance 4/0 — exact diameter in inches and millimeters, cross-section area, and copper resistance per 1,000 feet — with a live converter above the full printable chart.

174

Convert a wire gauge

On the default — 12 AWG — the diameter is 0.08081 in (2.053 mm), the cross-section 3.31 mm² (6,530 circular mils), about 1.588 Ω per 1,000 ft of solid copper. Enter any gauge below.

Gauge from 40 (thinnest) to 4/0 (thickest). Accepts 4/0, 0000, 2/0, or plain numbers.

Measured a wire instead? Enter its diameter to find the nearest standard gauge.

Result—Enter values above

Enter values to see the result.

How the gauge numbers work

AWG is a logarithmic scale: every 3 gauges, the cross-section roughly doubles; every 10 gauges, it grows about tenfold. The bigger the number, the thinner the wire — 40 AWG is hair-thin, 4/0 is thicker than your thumb. The exact diameter comes from the ASTM formula d = 0.005 × 92((36 − n) ÷ 39) inches, where n is the gauge (4/0 = −3, 3/0 = −2, 2/0 = −1, 1/0 = 0). Every number in the chart is computed from that formula — no rounded lookups.

Reading the columns

Diameter (in / mm) is what you measure with calipers. Area (mm²) and circular mils are what current capacity actually depends on — 1 kcmil (a thousand circular mils) = 0.5067 mm². Ω per 1,000 ft is the voltage-drop column: multiply by your run length to see what the wire itself eats.

Common gauges and what they’re for

Typical uses, not permissions: 18 AWG doorbells, thermostats, low-voltage; 16 extension cords and speaker wire; 14 lighting circuits; 12 receptacle circuits; 10 dryers, AC units, water heaters; 8–6 ranges and subpanels; 4–1 feeders; 1/0–4/0 service entrances. The NEC and your inspector have the final word on every one of these.

The full AWG chart

44 sizes, 40 AWG (hair-thin) to 4/0 (service-entrance). Diameters from the ASTM formula; resistance for solid annealed copper at 20 °C. Print it with Ctrl/Cmd+P — the table prints clean on one reference sheet.

AWGDiameter (in)Diameter (mm)Area (mm²)Circular milsΩ per 1,000 ft
4/00.4600011.684107.22.116e+050.04901
3/00.4096410.40585.031.678e+050.0618
2/00.364809.26667.431.331e+050.07793
1/00.324868.25153.481.055e+050.09827
10.289307.34842.418.369e+040.1239
20.257636.54433.636.637e+040.1563
30.229425.82726.675.263e+040.197
40.204315.18921.154.174e+040.2485
50.181944.62116.773.31e+040.3133
60.162024.11513.32.625e+040.3951
70.144293.66510.552.082e+040.4982
80.128493.2648.3661.651e+040.6282
90.114422.9066.6341.309e+040.7921
100.101902.5885.2611.038e+040.9988
110.090742.3054.17282341.26
120.080812.0533.30965301.588
130.071961.8282.62451782.003
140.064081.6282.08141072.525
150.057071.4501.6532573.184
160.050821.2911.30925834.015
170.045261.1501.03820485.063
180.040301.0240.82316246.385
190.035890.9120.652712888.051
200.031960.8120.5176102210.15
210.028460.7230.4105810.112.8
220.025350.6440.3255642.416.14
230.022570.5730.2582509.520.36
240.020100.5110.204740425.67
250.017900.4550.1624320.432.37
260.015940.4050.1288254.140.81
270.014200.3610.1021201.551.47
280.012640.3210.08098159.864.9
290.011260.2860.06422126.781.83
300.010030.2550.05093100.5103.2
310.008930.2270.0403979.7130.1
320.007950.2020.0320363.21164.1
330.007080.1800.025450.13206.9
340.006300.1600.0201439.75260.9
350.005610.1430.0159731.52329
360.005000.1270.0126725414.8
370.004450.1130.0100519.83523.1
380.003970.1010.00796715.72659.6
390.003530.0900.00631812.47831.8
400.003140.0800.005019.8881049

Output · formula · meaning

OutputFormulaWhat it means
Diameter0.005 × 92((36−n)÷39) in12 AWG → 0.08081 in (2.053 mm).
Cross-sectionπ × (mm ÷ 2)²Current capacity lives here: 3.31 mm² for 12 AWG.
Circular milsdiameter(in)² × 1,000,000The US wire trade’s area unit: 12 AWG = 6,530.
Resistance10.371 × 1,000 ÷ circular milsSolid copper at 20°C: 12 AWG = 1.588 Ω/1,000 ft.

Who uses this

  • Electricians: checking a gauge against conduit fill and voltage drop on the fly.
  • DIYers: making sure the wire they bought matches the breaker they’re feeding.
  • Automotive & RV installers: sizing 12-V runs where every milliohm matters.
  • Electronics hobbyists: picking hookup wire and checking resistance for a project.

Accuracy & limitations

Diameters are exact per the ASTM B258 definition of AWG; resistance figures are for solid annealed copper at 20°C — stranded wire and heat shift them slightly. Ampacity is deliberately excluded: safe current depends on insulation temperature rating, how many conductors share a conduit, and ambient temperature (NEC Article 310 and your local code govern). If you are sizing a circuit, stop at this chart and open the code book.

Measuring in decimals? The inches-to-fraction chart converts 0.0808 in to a tape-measure fraction, and the fraction-to-decimal chart goes the other way.

Cite this calculatorBright Side Kit. “Wire Gauge Chart: AWG to mm & Resistance” brightoolbox.com, 2026.Bright Side Kit. "Wire Gauge Chart: AWG to mm & Resistance" https://brightoolbox.com/wire-gauge-chart/ Accessed October 22, 2026.
Embed this calculator

Paste this into any web page to embed the live calculator. The “Bright Side Kit” link below it must stay intact.

Frequently asked questions

What does AWG mean?

American Wire Gauge — the US standard for wire thickness since 1857. It is backwards on purpose: a bigger gauge number means a thinner wire, because the number once counted how many times the wire was drawn through smaller dies.

What is 12 AWG in millimeters?

2.053 mm diameter, 3.31 mm² cross-section — the standard US wire for 20-amp receptacle circuits. Enter any gauge in the converter above for its exact metric size.

Which is thicker, 10 AWG or 12 AWG?

10 AWG — lower number, thicker wire. 10 AWG is 2.588 mm across versus 2.053 mm for 12 AWG, with about 60% more copper.

What gauge wire do I need for a 20-amp circuit?

Typically 12 AWG copper — the standard pairing in US residential wiring. But the breaker, the insulation rating, the run length, and your local code all matter; when any of those are unusual, check NEC Article 310 rather than the rule of thumb.

How is wire resistance calculated?

From copper’s resistivity: 10.371 ohms per circular-mil-foot. Divide by the wire’s circular mils and multiply by the length in feet. 12 AWG (6,530 circular mils) works out to about 1.588 Ω per 1,000 ft.

What is kcmil (MCM)?

A thousand circular mils — the unit for fat conductors where AWG runs out. 4/0 AWG is 211.6 kcmil; 1 kcmil = 0.5067 mm². MCM is the older name for the same unit.

Does stranded vs. solid change the gauge?

No — AWG measures the total copper cross-section, so a stranded 12 AWG and a solid 12 AWG are the same gauge. Stranding changes flexibility and slightly changes resistance, not the size designation.