Convert a wire gauge
On the default — 12 AWG — the diameter is 0.08081 in (2.053 mm), the cross-section 3.31 mm² (6,530 circular mils), about 1.588 Ω per 1,000 ft of solid copper. Enter any gauge below.
Enter values to see the result.
REFERENCE CHART · CONSTRUCTION
Every American Wire Gauge size from hair-thin 40 AWG to service-entrance 4/0 — exact diameter in inches and millimeters, cross-section area, and copper resistance per 1,000 feet — with a live converter above the full printable chart.
On the default — 12 AWG — the diameter is 0.08081 in (2.053 mm), the cross-section 3.31 mm² (6,530 circular mils), about 1.588 Ω per 1,000 ft of solid copper. Enter any gauge below.
Enter values to see the result.
AWG is a logarithmic scale: every 3 gauges, the cross-section roughly doubles; every 10 gauges, it grows about tenfold. The bigger the number, the thinner the wire — 40 AWG is hair-thin, 4/0 is thicker than your thumb. The exact diameter comes from the ASTM formula d = 0.005 × 92((36 − n) ÷ 39) inches, where n is the gauge (4/0 = −3, 3/0 = −2, 2/0 = −1, 1/0 = 0). Every number in the chart is computed from that formula — no rounded lookups.
Diameter (in / mm) is what you measure with calipers. Area (mm²) and circular mils are what current capacity actually depends on — 1 kcmil (a thousand circular mils) = 0.5067 mm². Ω per 1,000 ft is the voltage-drop column: multiply by your run length to see what the wire itself eats.
Typical uses, not permissions: 18 AWG doorbells, thermostats, low-voltage; 16 extension cords and speaker wire; 14 lighting circuits; 12 receptacle circuits; 10 dryers, AC units, water heaters; 8–6 ranges and subpanels; 4–1 feeders; 1/0–4/0 service entrances. The NEC and your inspector have the final word on every one of these.
44 sizes, 40 AWG (hair-thin) to 4/0 (service-entrance). Diameters from the ASTM formula; resistance for solid annealed copper at 20 °C. Print it with Ctrl/Cmd+P — the table prints clean on one reference sheet.
| AWG | Diameter (in) | Diameter (mm) | Area (mm²) | Circular mils | Ω per 1,000 ft |
|---|---|---|---|---|---|
| 4/0 | 0.46000 | 11.684 | 107.2 | 2.116e+05 | 0.04901 |
| 3/0 | 0.40964 | 10.405 | 85.03 | 1.678e+05 | 0.0618 |
| 2/0 | 0.36480 | 9.266 | 67.43 | 1.331e+05 | 0.07793 |
| 1/0 | 0.32486 | 8.251 | 53.48 | 1.055e+05 | 0.09827 |
| 1 | 0.28930 | 7.348 | 42.41 | 8.369e+04 | 0.1239 |
| 2 | 0.25763 | 6.544 | 33.63 | 6.637e+04 | 0.1563 |
| 3 | 0.22942 | 5.827 | 26.67 | 5.263e+04 | 0.197 |
| 4 | 0.20431 | 5.189 | 21.15 | 4.174e+04 | 0.2485 |
| 5 | 0.18194 | 4.621 | 16.77 | 3.31e+04 | 0.3133 |
| 6 | 0.16202 | 4.115 | 13.3 | 2.625e+04 | 0.3951 |
| 7 | 0.14429 | 3.665 | 10.55 | 2.082e+04 | 0.4982 |
| 8 | 0.12849 | 3.264 | 8.366 | 1.651e+04 | 0.6282 |
| 9 | 0.11442 | 2.906 | 6.634 | 1.309e+04 | 0.7921 |
| 10 | 0.10190 | 2.588 | 5.261 | 1.038e+04 | 0.9988 |
| 11 | 0.09074 | 2.305 | 4.172 | 8234 | 1.26 |
| 12 | 0.08081 | 2.053 | 3.309 | 6530 | 1.588 |
| 13 | 0.07196 | 1.828 | 2.624 | 5178 | 2.003 |
| 14 | 0.06408 | 1.628 | 2.081 | 4107 | 2.525 |
| 15 | 0.05707 | 1.450 | 1.65 | 3257 | 3.184 |
| 16 | 0.05082 | 1.291 | 1.309 | 2583 | 4.015 |
| 17 | 0.04526 | 1.150 | 1.038 | 2048 | 5.063 |
| 18 | 0.04030 | 1.024 | 0.823 | 1624 | 6.385 |
| 19 | 0.03589 | 0.912 | 0.6527 | 1288 | 8.051 |
| 20 | 0.03196 | 0.812 | 0.5176 | 1022 | 10.15 |
| 21 | 0.02846 | 0.723 | 0.4105 | 810.1 | 12.8 |
| 22 | 0.02535 | 0.644 | 0.3255 | 642.4 | 16.14 |
| 23 | 0.02257 | 0.573 | 0.2582 | 509.5 | 20.36 |
| 24 | 0.02010 | 0.511 | 0.2047 | 404 | 25.67 |
| 25 | 0.01790 | 0.455 | 0.1624 | 320.4 | 32.37 |
| 26 | 0.01594 | 0.405 | 0.1288 | 254.1 | 40.81 |
| 27 | 0.01420 | 0.361 | 0.1021 | 201.5 | 51.47 |
| 28 | 0.01264 | 0.321 | 0.08098 | 159.8 | 64.9 |
| 29 | 0.01126 | 0.286 | 0.06422 | 126.7 | 81.83 |
| 30 | 0.01003 | 0.255 | 0.05093 | 100.5 | 103.2 |
| 31 | 0.00893 | 0.227 | 0.04039 | 79.7 | 130.1 |
| 32 | 0.00795 | 0.202 | 0.03203 | 63.21 | 164.1 |
| 33 | 0.00708 | 0.180 | 0.0254 | 50.13 | 206.9 |
| 34 | 0.00630 | 0.160 | 0.02014 | 39.75 | 260.9 |
| 35 | 0.00561 | 0.143 | 0.01597 | 31.52 | 329 |
| 36 | 0.00500 | 0.127 | 0.01267 | 25 | 414.8 |
| 37 | 0.00445 | 0.113 | 0.01005 | 19.83 | 523.1 |
| 38 | 0.00397 | 0.101 | 0.007967 | 15.72 | 659.6 |
| 39 | 0.00353 | 0.090 | 0.006318 | 12.47 | 831.8 |
| 40 | 0.00314 | 0.080 | 0.00501 | 9.888 | 1049 |
| Output | Formula | What it means |
|---|---|---|
| Diameter | 0.005 × 92((36−n)÷39) in | 12 AWG → 0.08081 in (2.053 mm). |
| Cross-section | π × (mm ÷ 2)² | Current capacity lives here: 3.31 mm² for 12 AWG. |
| Circular mils | diameter(in)² × 1,000,000 | The US wire trade’s area unit: 12 AWG = 6,530. |
| Resistance | 10.371 × 1,000 ÷ circular mils | Solid copper at 20°C: 12 AWG = 1.588 Ω/1,000 ft. |
Diameters are exact per the ASTM B258 definition of AWG; resistance figures are for solid annealed copper at 20°C — stranded wire and heat shift them slightly. Ampacity is deliberately excluded: safe current depends on insulation temperature rating, how many conductors share a conduit, and ambient temperature (NEC Article 310 and your local code govern). If you are sizing a circuit, stop at this chart and open the code book.
Measuring in decimals? The inches-to-fraction chart converts 0.0808 in to a tape-measure fraction, and the fraction-to-decimal chart goes the other way.
Bright Side Kit. "Wire Gauge Chart: AWG to mm & Resistance" https://brightoolbox.com/wire-gauge-chart/ Accessed October 22, 2026.American Wire Gauge — the US standard for wire thickness since 1857. It is backwards on purpose: a bigger gauge number means a thinner wire, because the number once counted how many times the wire was drawn through smaller dies.
2.053 mm diameter, 3.31 mm² cross-section — the standard US wire for 20-amp receptacle circuits. Enter any gauge in the converter above for its exact metric size.
10 AWG — lower number, thicker wire. 10 AWG is 2.588 mm across versus 2.053 mm for 12 AWG, with about 60% more copper.
Typically 12 AWG copper — the standard pairing in US residential wiring. But the breaker, the insulation rating, the run length, and your local code all matter; when any of those are unusual, check NEC Article 310 rather than the rule of thumb.
From copper’s resistivity: 10.371 ohms per circular-mil-foot. Divide by the wire’s circular mils and multiply by the length in feet. 12 AWG (6,530 circular mils) works out to about 1.588 Ω per 1,000 ft.
A thousand circular mils — the unit for fat conductors where AWG runs out. 4/0 AWG is 211.6 kcmil; 1 kcmil = 0.5067 mm². MCM is the older name for the same unit.
No — AWG measures the total copper cross-section, so a stranded 12 AWG and a solid 12 AWG are the same gauge. Stranding changes flexibility and slightly changes resistance, not the size designation.