Pick a wire size and insulation rating — get the allowable amps plus the max breaker.
REFERENCE TABLE · CONSTRUCTION · ELECTRICAL
How many amps each copper wire size can safely carry — the numbers electricians actually look up, from NEC Table 310.16, with the two rules that trip up DIYers baked in. Rule one: the insulation’s temperature rating decides which column you read (THHN reads the 90°C column, but your breaker’s terminals usually cap you at 75°C). Rule two: 14, 12, and 10 AWG copper can never take more than a 15, 20, or 30-amp breaker — NEC 240.4(D) — even though the table lists higher ampacities. Below: the full printable chart, a breaker-to-wire finder, and three live lookups. At the defaults, 12 AWG THHN carries 30 amps but still maxes out at a 20-amp breaker.
Pick a wire size and insulation rating — get the allowable amps plus the max breaker.
Know the breaker? Get the minimum copper wire size for it.
Pick a wire size — get the largest breaker NEC allows on it.
NEC 2023 Table 310.16, copper conductors — up to three current-carrying conductors at 30°C (86°F) ambient. Print this for the job site:
| Wire size | 60°C | 75°C | 90°C | Max breaker |
|---|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A | 15 A |
| 12 AWG | 20 A | 25 A | 30 A | 20 A |
| 10 AWG | 30 A | 35 A | 40 A | 30 A |
| 8 AWG | 40 A | 50 A | 55 A | 50 A |
| 6 AWG | 55 A | 65 A | 75 A | 65 A |
| 4 AWG | 70 A | 85 A | 95 A | 85 A |
| 3 AWG | 85 A | 100 A | 115 A | 100 A |
| 2 AWG | 95 A | 115 A | 130 A | 115 A |
| 1 AWG | 110 A | 130 A | 145 A | 130 A |
| 1/0 AWG | 125 A | 150 A | 170 A | 150 A |
| 2/0 AWG | 145 A | 175 A | 195 A | 175 A |
| 3/0 AWG | 165 A | 200 A | 225 A | 200 A |
| 4/0 AWG | 195 A | 230 A | 260 A | 230 A |
How to read it: find your wire size, then read the column matching the wire’s insulation rating — but never above what the breaker and device terminals are rated for (NEC 110.14(C); most residential gear is 75°C). The Max breaker column is the overcurrent limit: for 14/12/10 AWG that’s the 240.4(D) small-conductor cap, for 8 AWG and up it’s the termination-limited ampacity. Long runs need upsizing for voltage drop — ampacity is heat, not distance.
| Breaker | NM-B (Romex) | THHN in conduit |
|---|---|---|
| 15 A | 14 AWG | 14 AWG |
| 20 A | 12 AWG | 12 AWG |
| 30 A | 10 AWG | 10 AWG |
| 40 A | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG |
| 60 A | 4 AWG | 6 AWG |
| 100 A | 1 AWG | 3 AWG |
| Output | Formula | What it means |
|---|---|---|
| Ampacity | Table 310.16 lookup (size × temp column) | The max continuous current: 30 A for 12 AWG at 90°C. |
| Max breaker | min(ampacity, 240.4(D) cap) | The largest overcurrent device allowed: 20 A on 12 AWG. |
| Min wire for breaker | smallest AWG with ampacity ≥ breaker | A 30 A breaker needs at least 10 AWG copper. |
Values are NEC 2023 Table 310.16 for copper at 30°C ambient with up to three current-carrying conductors — the starting point, not always the final answer. Hot attics, bundled cables, and continuous loads (over 3 hours) require derating that can drop a size. Aluminum runs about one size larger for the same amps. Local amendments may differ; your AHJ (authority having jurisdiction) has the last word. This is a reference, not a permit — when in doubt, hire a licensed electrician.
Bright Side Kit. "Wire Gauge Ampacity Chart: NEC 310.16." https://brightoolbox.com/wire-gauge-ampacity-chart/ Accessed October 23, 2026.Because of NEC 240.4(D), the small-conductor rule: overcurrent protection on 14, 12, and 10 AWG copper is capped at 15, 20, and 30 amps respectively, regardless of what the 90°C column says. The table lists the wire’s heat capacity (30 A for 12 AWG at 90°C); the rule limits the breaker. The lookup above shows both numbers so the distinction is never missed.
They match the wire’s insulation temperature rating: TW/UF jackets read the 60°C column, THW/XHHW the 75°C column, THHN/THWN-2 the 90°C column. Hotter-rated insulation lets the same copper carry more current. But NEC 110.14(C) adds the catch: you can’t use a column hotter than your breaker and device terminals are rated for — and most residential gear is 75°C, so the 90°C column is usually just a starting point for derating math.
Only if every termination is 90°C-rated too — the wire, the breaker lugs, and the device. In homes, that’s rare: NM-B (Romex) is a 60°C wiring method, and standard breakers and receptacles are 75°C. The honest rule: read the column your weakest component allows. The 90°C column still matters — it’s the starting point when derating for hot attics or bundled cables.
Aluminum carries less current per size — roughly one AWG size larger than copper for the same amps (12 AWG aluminum ≈ 14 AWG copper at 15 A). This page’s chart and lookups are copper only; aluminum has its own Table 310.16 columns and needs antioxidant paste and CO/ALR-rated devices at terminations. Size aluminum separately.
No \u2014 but it changes the wire you should buy. Ampacity is about heat: how much current the wire can carry without overheating its insulation. Length causes voltage drop, a separate problem — a long run at full ampacity can still starve the load of volts. Rule of thumb: runs over ~100 feet at 120 V often need one size up for voltage drop even when the ampacity table says the smaller wire is fine.
It’s the starting point. Table 310.16 assumes 30°C ambient and at most three current-carrying conductors. Hot attics, conduit stuffed with circuits, and continuous loads (3+ hours, like EV chargers) all require derating that can cost you a wire size. Local code amendments can differ, and your inspector (the AHJ) has the last word. Treat this as the reference the pros start from — not a substitute for one.