Pipe size chart — OD, wall, ID, area, and flow
A 1 inch Schedule 40 pipe has a 1.315 inch outside diameter, a 1.049 inch inside diameter, and carries 13.47 GPM at 5 ft/s. Pick a size and schedule below.
★ CONSTRUCTION · PLUMBING · REFERENCE
A 1 inch Schedule 40 pipe is 1.315 inches outside, 1.049 inches inside, and carries 13.47 GPM at 5 ft/s. Pick any size from 1/8 inch to 6 inch and either schedule to get its OD, wall, ID, area, and flow — dimensions from ASME B36.10M.
A 1 inch Schedule 40 pipe has a 1.315 inch outside diameter, a 1.049 inch inside diameter, and carries 13.47 GPM at 5 ft/s. Pick a size and schedule below.
Pipe is sold by nominal size, and the nominal size is not a measurement of anything on the pipe: a 1 inch pipe is not 1 inch across. What is fixed is the outside diameter (OD), which is the same for every schedule of a given nominal size — a 1 inch pipe is always 1.315 inches outside, whether it is Schedule 40 or Schedule 80. What changes with the schedule is the wall thickness: Schedule 80 walls are thicker, so the inside diameter (ID) is smaller, the bore is smaller, and the pipe carries less water at the same velocity. The inside diameter is simply OD minus twice the wall thickness, and the flow comes from the bore area times the velocity.
At the defaults — a 1 inch Schedule 40 pipe — the OD is 1.315 inches and the wall is 0.133 inches, so the ID is 1.315 − 2 × 0.133 = 1.049 inches. The cross-section area is π/4 × 1.049² = 0.864 square inches, and at 5 feet per second that bore carries 5 × (0.864 / 144) × 448.831 = 13.47 gallons per minute. The 448.831 is the conversion from cubic feet per second to gallons per minute, and the 144 converts square inches to square feet. All dimensions on this page follow ASME B36.10M, the standard for welded and seamless wrought steel pipe.
| Nominal size | OD (in) | Wall (in) | ID (in) | Area (in²) | Flow at 5 ft/s (GPM) |
|---|---|---|---|---|---|
| 1/8 inch | 0.405 | 0.068 | 0.269 | 0.057 | 0.89 |
| 1/4 inch | 0.540 | 0.088 | 0.364 | 0.104 | 1.62 |
| 3/8 inch | 0.675 | 0.091 | 0.493 | 0.191 | 2.97 |
| 1/2 inch | 0.840 | 0.109 | 0.622 | 0.304 | 4.74 |
| 3/4 inch | 1.050 | 0.113 | 0.824 | 0.533 | 8.31 |
| 1 inch | 1.315 | 0.133 | 1.049 | 0.864 | 13.47 |
| 1-1/4 inch | 1.660 | 0.140 | 1.380 | 1.496 | 23.31 |
| 1-1/2 inch | 1.900 | 0.145 | 1.610 | 2.036 | 31.73 |
| 2 inch | 2.375 | 0.154 | 2.067 | 3.356 | 52.30 |
| 2-1/2 inch | 2.875 | 0.203 | 2.469 | 4.788 | 74.61 |
| 3 inch | 3.500 | 0.216 | 3.068 | 7.393 | 115.21 |
| 4 inch | 4.500 | 0.237 | 4.026 | 12.730 | 198.39 |
| 5 inch | 5.563 | 0.258 | 5.047 | 20.006 | 311.78 |
| 6 inch | 6.625 | 0.280 | 6.065 | 28.890 | 450.24 |
Schedule 40 dimensions above are from ASME B36.10M. Flow is the maximum at 5 feet per second, the usual design velocity for water supply; faster water is noisier and wears fittings out.
| Nominal size | OD (in) | Wall (in) | ID (in) | Area (in²) | Flow at 5 ft/s (GPM) |
|---|---|---|---|---|---|
| 1/8 inch | 0.405 | 0.095 | 0.215 | 0.036 | 0.57 |
| 1/4 inch | 0.540 | 0.119 | 0.302 | 0.072 | 1.12 |
| 3/8 inch | 0.675 | 0.126 | 0.423 | 0.141 | 2.19 |
| 1/2 inch | 0.840 | 0.147 | 0.546 | 0.234 | 3.65 |
| 3/4 inch | 1.050 | 0.154 | 0.742 | 0.432 | 6.74 |
| 1 inch | 1.315 | 0.179 | 0.957 | 0.719 | 11.21 |
| 1-1/4 inch | 1.660 | 0.191 | 1.278 | 1.283 | 19.99 |
| 1-1/2 inch | 1.900 | 0.200 | 1.500 | 1.767 | 27.54 |
| 2 inch | 2.375 | 0.218 | 1.939 | 2.953 | 46.02 |
| 2-1/2 inch | 2.875 | 0.276 | 2.323 | 4.238 | 66.05 |
| 3 inch | 3.500 | 0.300 | 2.900 | 6.605 | 102.94 |
| 4 inch | 4.500 | 0.337 | 3.826 | 11.497 | 179.17 |
| 5 inch | 5.563 | 0.375 | 4.813 | 18.194 | 283.54 |
| 6 inch | 6.625 | 0.432 | 5.761 | 26.067 | 406.23 |
Schedule 80 dimensions above are from ASME B36.10M. The outside diameter is the same as Schedule 40 for every size; only the wall is thicker, so every ID, area, and flow is smaller.
Setup: nominal size 1 inch; schedule Schedule 40; required flow 50 GPM.
Line 1 — the outside diameter. A 1 inch pipe is 1.315 inches outside, whatever the schedule. Nominal size is a name, not a measurement.
Line 2 — the inside diameter. ID = OD − 2 × wall = 1.315 − 2 × 0.133 = 1.049 inches.
Line 3 — the cross-section area. Area = π/4 × ID² = 0.785398 × 1.049² = 0.864 square inches.
Line 4 — the flow. Flow = 5 ft/s × (0.8643 / 144) ft² × 448.831 = 13.47 GPM. The 144 converts square inches to square feet; 448.831 converts cubic feet per second to gallons per minute.
Line 5 — the reverse. A 1-1/2 inch Schedule 40 pipe carries only 31.73 GPM at 5 ft/s, which is short of 50 GPM, so the smallest pipe that meets the requirement is a 2 inch Schedule 40 pipe, which carries 52.30 GPM.
1/2 inch Schedule 40: OD 0.840 inches, wall 0.109 inches, ID 0.840 − 2 × 0.109 = 0.622 inches, area π/4 × 0.622² = 0.304 square inches, flow 4.74 GPM at 5 ft/s. A half-inch line feeds a single fixture, not a house.
2 inch Schedule 40: OD 2.375 inches, wall 0.154 inches, ID 2.067 inches, area 3.356 square inches, flow 52.30 GPM at 5 ft/s. Going from 1-1/2 inch to 2 inch nearly doubles the flow, because area grows with the square of the diameter.
4 inch Schedule 40: OD 4.500 inches, wall 0.237 inches, ID 4.026 inches, area 12.730 square inches, flow 198.39 GPM at 5 ft/s. A 4 inch main carries almost four times what a 2 inch line carries.
1 inch Schedule 80: the wall is 0.179 inches instead of 0.133, so the ID is 1.315 − 2 × 0.179 = 0.957 inches, the area is 0.719 square inches, and the flow is 11.21 GPM at 5 ft/s — about 17% less than the same nominal size in Schedule 40, the price of the thicker wall.
Reverse — 50 GPM: the smallest Schedule 40 pipe that carries 50 GPM at 5 ft/s is the 2 inch pipe at 52.30 GPM. The 1-1/2 inch pipe manages only 31.73 GPM, so it is not close.
Dimensions are nominal ASME B36.10M values for steel pipe, in inches; copper, PVC, and PEX use different sizing systems, so do not read this chart against a copper or plastic pipe — see the copper pipe size chart and the PVC pipe size chart for those. Flow is the maximum at 5 feet per second with a full, unobstructed bore: fittings, elbows, valves, and scale all reduce real flow, and water over about 5 ft/s is noisy and wears fittings, so 5 ft/s is a design limit, not a target to exceed. The reverse lookup uses Schedule 40 only, because that is the usual water-supply schedule; a Schedule 80 pipe of the same nominal size always carries less. Rounding convention: diameters and walls to three decimals, areas to three decimals, flows to two decimals, all computed from unrounded values.
| Output | Formula | What it means |
|---|---|---|
| Outside diameter (OD) | ASME B36.10M, fixed per nominal size | 1.315 in for 1 inch pipe, either schedule. |
| Wall thickness | ASME B36.10M, by schedule | 0.133 in for 1 inch Schedule 40. |
| Inside diameter (ID) | OD − 2 × wall | 1.049 in for 1 inch Schedule 40. |
| Cross-section area | π/4 × ID² | 0.864 in² for 1 inch Schedule 40. |
| Max flow at 5 ft/s | 5 × area/144 × 448.831 | 13.47 GPM for 1 inch Schedule 40. |
| 1/2 inch Sch 40 | same formulas | 0.622 in ID; 4.74 GPM. |
| 2 inch Sch 40 | same formulas | 2.067 in ID; 52.30 GPM. |
| 4 inch Sch 40 | same formulas | 4.026 in ID; 198.39 GPM. |
| 1 inch Sch 80 | same formulas, wall 0.179 in | 0.957 in ID; 0.719 in²; 11.21 GPM. |
| Reverse: 50 GPM | smallest Sch 40 flow ≥ 50 GPM | 2 inch (52.30 GPM). |
The dimensions are ASME B36.10M nominal values: OD and wall are exact to the thousandths of an inch shown, ID is OD minus twice the wall, area is π/4 times ID squared, and flow is 5 ft/s times the bore area in square feet times 448.831 gallons per minute per cubic foot per second. What the chart cannot do is replace a hydraulic calculation: real flow depends on pressure, pipe length, fittings, elevation, and water temperature, and the 5 ft/s figure is a design velocity, not a guarantee. It also covers steel pipe only: copper, PVC, CPVC, and PEX have their own sizing tables, and a 1 inch copper pipe is not 1.315 inches outside. Read the NPT pipe thread chart for the threads that match these sizes.
Bright Side Kit. "Pipe Size Chart: Nominal Size, OD, ID & Flow (Sch 40/80)" https://brightoolbox.com/pipe-size-chart/ Accessed October 24, 2026.No — a 1 inch pipe is 1.315 inches across on the outside. Nominal size is a name, not a measurement: it comes from the old inside diameter of the pipe, and the outside diameter has stayed fixed while walls got thinner. Measure the outside diameter and look it up in the chart to find the nominal size.
The wall thickness. Schedule 80 walls are thicker, so the pipe holds more pressure but the inside diameter is smaller. A 1 inch Schedule 80 pipe has a 0.957 inch bore and carries 11.21 GPM at 5 ft/s, against a 1.049 inch bore and 13.47 GPM for Schedule 40.
OD minus twice the wall thickness. For a 1 inch Schedule 40 pipe that is 1.315 − 2 × 0.133 = 1.049 inches. The wall takes space from both sides of the bore, which is why it is doubled.
Because flow follows the bore area, and area grows with the square of the diameter. A 1 inch Schedule 40 pipe carries 13.47 GPM and a 2 inch one carries 52.30 GPM at the same 5 ft/s — 3.9 times as much, because the bore area is 3.356 square inches against 0.864.
A 2 inch Schedule 40 pipe, which carries 52.30 GPM at 5 ft/s. A 1-1/2 inch pipe only carries 31.73 GPM, so it falls well short. Enter your own required flow in the calculator and it finds the smallest size that meets it.
5 ft/s is the usual design velocity for water supply. Faster water is noisy, hammers when taps close, and wears fittings and elbows out. The flow in the chart is the maximum at that velocity, not a target to exceed.
No — this chart is for steel pipe to ASME B36.10M. Copper, PVC, CPVC, and PEX use different sizing systems, and a 1 inch copper pipe is not 1.315 inches outside. Use the copper pipe size chart or the PVC pipe size chart for those materials.
OD is the outside diameter, and it is fixed so fittings fit either schedule. A 1 inch pipe is 1.315 inches outside whether it is Schedule 40 or Schedule 80, so the same fittings, flanges, and threads work with both. Only the wall — and therefore the bore — changes.