★ CONSTRUCTION · WIRE SIZE · REFERENCE TABLE #246

Electrical Wire Size Chart: Ampacity & Voltage Drop 2026

Recommended 10 AWG — ampacity needs 12 AWG, voltage drop needs 10 AWG. A 20-amp load 50 feet away needs 10 AWG, not 12 — 12 AWG carries the current fine, but its voltage drop is 3.29%, over the 3% limit. Enter your load, distance and voltage to find your gauge.

970

Electrical wire size chart

What size wire do you need? Enter the load current, the one-way distance and the voltage to find the minimum gauge by ampacity and voltage drop, with the full NEC copper table.

The load current the wire must carry, in amps — the breaker or the load rating. The default is 20 A.

The one-way distance from the panel to the load, in feet — the wire runs there and back, so the voltage drop counts both ways. The default is 50 ft.

The circuit voltage — 120 V for a standard household circuit, 240 V for a large appliance or subpanel. Higher voltage means less drop for the same load. The default is 120 V.

The maximum voltage drop you will accept, in percent — 3% is the NEC informational recommendation for a branch circuit. The default is 3%.

Recommended 10 AWG — ampacity 12 AWG, voltage drop 10 AWGRecommended 10 AWG — ampacity 12 AWG, voltage drop 10 AWGRecommended gauge 10 AWG. Ampacity gauge 12 AWG. Drop gauge 10 AWG. Voltage drop at the recommended gauge 2.4855 V / 2.07%. Voltage drop at the ampacity gauge 3.9510 V / 3.29%. The recommended gauge is the larger wire of the ampacity gauge and the drop gauge — voltage drop, not ampacity, usually sizes the wire on long runs. The 3% limit is the NEC informational recommendation, not a code requirement. Always check local code and get a licensed electrician for service work. Rounding convention: totals are computed from unrounded values, so rounded parts may differ by a cent from their rounded sum.

Ampacity gauge: 12 AWG

Drop gauge: 10 AWG

Recommended gauge: 10 AWG

Voltage drop at the recommended gauge: 2.4855 V / 2.07%

Voltage drop at the ampacity gauge: 3.9510 V / 3.29%

Voltage drop at the drop gauge: 2.4855 V / 2.07%

Branch: Load 15 A: Amp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47%

Branch: Load 30 A: Amp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95%

Branch: Distance 100 ft: Amp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60%

Branch: Voltage 240 V: Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65%

Branch: Load 100 A: Amp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28%

Branch: Max drop 5%: Amp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29%

Reverse: distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V: 45.5581 (45.56 ft) — the star is a DISTANCE

At 45.55 ft the drop is: 2.9995%

At 45.56 ft it is: 3.0001%

At 45.57 ft it is: 3.0008%

Reverse verdict: NEAREST

Reverse: current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V: 28.9674 (28.97 A) — the star is a CURRENT

At 28.96 A the drop is: 2.9992%

At 28.97 A it is: 3.0003%

Reverse verdict: NEAREST

Reverse: distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V: 38.2326 (38.23 ft)

At 38.23 ft the drop is: 2.9998%

At 38.24 ft it is: 3.0006%

Reverse verdict: NEAREST

Reverse: current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V: 23.0372 (23.04 A)

At 23.03 A the drop is: 2.9991%

At 23.04 A it is: 3.0004%

Reverse verdict: NEAREST

Reverse: distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V: 91.1163 (91.12 ft)

At 91.11 ft the drop is: 2.9998%

At 91.12 ft it is: 3.0001%

Reverse verdict: NEAREST

Reverse: distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V: 48.2791 (48.28 ft)

At 48.27 ft the drop is: 2.9994%

At 48.28 ft it is: 3.0001%

Reverse verdict: NEAREST

Edge: 0 A load: Amp 14 AWG, drop 14 AWG, recommended 14 AWG, VD 0.00%

Edge: 0 ft distance: Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 0.00%

Edge: 200 A load: Amp none, drop 1 AWG, recommended none, VD —

Edge: voltage drop at 4/0 AWG on 200 A: 1.2193 V / 1.02%

Use 10 AWG — ampacity needs 12 AWG, voltage drop needs 10 AWG. At the recommended gauge the drop is 2.07%; at the ampacity gauge it is 3.29% — over the 3% limit, so the smaller wire fails on drop even though it carries the current.

Load 15 A: Amp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47%.

Load 30 A: Amp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95%.

Distance 100 ft: Amp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60%.

Voltage 240 V: Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65%.

Load 100 A: Amp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28%.

Max drop 5%: Amp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29%.

Reverse: the distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V is 45.56 ft (exact 45.5581 ft); at 45.55 ft the drop is 2.9995%, at 45.56 ft it is 3.0001%, at 45.57 ft it is 3.0008%. The current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V is 28.97 A (exact 28.9674 A); at 28.96 A the drop is 2.9992%, at 28.97 A it is 3.0003%. The distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V is 38.23 ft (exact 38.2326 ft); at 38.23 ft the drop is 2.9998%, at 38.24 ft it is 3.0006%. The current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V is 23.04 A (exact 23.0372 A); at 23.03 A the drop is 2.9991%, at 23.04 A it is 3.0004%. The distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V is 91.12 ft (exact 91.1163 ft); at 91.11 ft the drop is 2.9998%, at 91.12 ft it is 3.0001%. The distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V is 48.28 ft (exact 48.2791 ft); at 48.27 ft the drop is 2.9994%, at 48.28 ft it is 3.0001%.

Voltage drop, not ampacity, sizes the wire

Two limits decide a wire’s size, and they are not the same. Ampacity is how much current the wire can carry without overheating — 12 AWG carries 20 A. Voltage drop is how much voltage the wire itself eats on the way there and back — and on a long run it is the binding limit. On the defaults — load 20 A, distance 50 ft, voltage 120 V, max drop 3% — the ampacity gauge is 12 AWG, the drop gauge is 10 AWG, the recommended gauge is 10 AWG, the voltage drop at the recommended gauge is 2.4855 V / 2.07% and the voltage drop at the ampacity gauge is 3.9510 V / 3.29% — over 3%, so 12 AWG fails on drop.

Electrical wire size chart — NEC Table 310.16, 60°C copper

GaugeAmpacityCircular milsMax distance at 20 A / 120 V / 3%
14 AWG15 A4,11028.67 ft
12 AWG20 A6,53045.56 ft
10 AWG30 A10,38072.42 ft
8 AWG40 A16,510115.19 ft
6 AWG55 A26,240183.07 ft
4 AWG70 A41,740291.21 ft
3 AWG85 A52,620367.12 ft
2 AWG95 A66,360462.98 ft
1 AWG110 A83,690583.88 ft
1/0 AWG125 A105,600736.74 ft
2/0 AWG145 A133,100928.60 ft
3/0 AWG165 A167,8001,170.70 ft
4/0 AWG195 A211,6001,476.28 ft

At the defaults — load 20 A, distance 50 ft, voltage 120 V, max drop 3% — the ampacity gauge is 12 AWG, the drop gauge is 10 AWG, the recommended gauge is 10 AWG, the voltage drop at the recommended gauge is 2.4855 V / 2.07% and the voltage drop at the ampacity gauge is 3.9510 V / 3.29%. Check the identities: VD = 2 × 12.9 × I × L / CM; VD% = VD / V × 100; Lmax = 3.6 × CM / 516 at 20 A / 120 V / 3%; recommended = larger wire of amp gauge and drop gauge. Rounding convention: totals are computed from unrounded values, so rounded parts may differ by a cent from their rounded sum.

ScenarioAmpacityDropRecommendedVD% at recommended
Default (20 A, 50 ft, 120 V, 3%)12 AWG10 AWG10 AWG2.07%
Load 15 A14 AWG12 AWG12 AWG2.47%
Load 30 A10 AWG8 AWG8 AWG1.95%
Distance 100 ft12 AWG8 AWG8 AWG2.60%
Voltage 240 V12 AWG14 AWG12 AWG1.65%
Load 100 A1 AWG4 AWG1 AWG1.28%
Max drop 5%12 AWG12 AWG12 AWG3.29%

The worked example, line by line

Setup: load 20 A, distance 50 ft, voltage 120 V, max drop 3%.

Line 1 — the ampacity gauge. 12 AWG carries 20 A, so the ampacity gauge is 12 AWG.

Line 2 — the voltage drop on 12 AWG. VD = 2 × 12.9 × 20 × 50 / 6,530 = 3.9510 V. As a percentage: 3.9510 / 120 × 100 = 3.29% — over the 3% limit, so 12 AWG fails on drop.

Line 3 — the drop gauge. The next size up, 10 AWG, has 10,380 circular mils: VD = 2 × 12.9 × 20 × 50 / 10,380 = 2.4855 V, which is 2.07% — inside the limit, so the drop gauge is 10 AWG.

Line 4 — the recommendation. The recommended gauge is the larger wire of the two — 10 AWG. The 3% limit is the NEC informational recommendation, not a code requirement.

Reverse: the distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V is 45.56 ft (exact 45.5581 ft); at 45.55 ft the drop is 2.9995%, at 45.56 ft it is 3.0001%, at 45.57 ft it is 3.0008%. The current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V is 28.97 A (exact 28.9674 A); at 28.96 A the drop is 2.9992%, at 28.97 A it is 3.0003%. The distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V is 38.23 ft (exact 38.2326 ft); at 38.23 ft the drop is 2.9998%, at 38.24 ft it is 3.0006%. The current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V is 23.04 A (exact 23.0372 A); at 23.03 A the drop is 2.9991%, at 23.04 A it is 3.0004%. The distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V is 91.12 ft (exact 91.1163 ft); at 91.11 ft the drop is 2.9998%, at 91.12 ft it is 3.0001%. The distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V is 48.28 ft (exact 48.2791 ft); at 48.27 ft the drop is 2.9994%, at 48.28 ft it is 3.0001%.

Every branch, checked

Load 15 A: Amp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47%. 14 AWG carries 15 A, but its drop is 3.92% — over the limit — so the drop gauge is 12 AWG at 2.47%.

Load 30 A: Amp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95%. 10 AWG carries 30 A, but its drop is 3.11% — over the limit — so the drop gauge is 8 AWG at 1.95%.

Distance 100 ft: Amp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60%. Doubling the distance doubles the drop: 12 AWG is 6.58%, 10 AWG is 4.14%, and only 8 AWG at 2.60% passes.

Voltage 240 V: Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65%. At 240 V the drop halves, so the drop gauge is 14 AWG — SMALLER than the ampacity gauge — and the recommendation stays 12 AWG, the larger wire.

Load 100 A: Amp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28%. The drop passes on 4 AWG, but ampacity requires 1 AWG — the drop gauge is smaller than the ampacity gauge again, and the recommendation is the larger wire, 1 AWG.

Max drop 5%: Amp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29%. At a 5% limit 12 AWG passes with a 3.29% drop, so the ampacity and drop gauges agree at 12 AWG.

What the defaults assume

The model assumes single-phase copper conductors, K = 12.9, the NEC Table 310.16 60°C column, and a one-way distance — the wire runs there and back, so the voltage drop counts both ways. It assumes the load is continuous at the current you enter and the temperature is within the 60°C column’s range — it does not model derating for bundled cables, high ambient temperature, or aluminum wire, which needs larger gauges. With a 0 A load the ampacity gauge is 14 AWG, the recommended gauge is 14 AWG and the voltage drop is 0.00% — no load, no drop. With a 0 ft distance the recommended gauge is 12 AWG and the voltage drop is 0.00%. With a 200 A load the ampacity gauge is none — 4/0 AWG maxes at 195 A, so no single copper gauge in the table carries 200 A (parallel runs or larger service wire needed); the voltage drop at 4/0 is only 1.02% — drop is fine, ampacity is the binding limit. Rounding convention: totals are computed from unrounded values, so rounded parts may differ by a cent from their rounded sum; the reverses are nearest-value solutions, and the exact unrounded figures (45.5581, 28.9674, 38.2326, 23.0372, 91.1163, 48.2791) are stated wherever the rounded figures appear.

Output · formula · meaning

OutputFormulaWhat it means
Ampacity gaugethe smallest gauge whose ampacity ≥ load12 AWG.
Drop gaugethe smallest gauge whose VD% ≤ max drop10 AWG.
Recommended gaugethe larger wire of the ampacity gauge and the drop gauge10 AWG.
Voltage drop at the recommended gauge2 × 12.9 × I × L / CM, then ÷ V × 1002.4855 V.
Voltage drop % at the recommended gaugeVD ÷ V × 1002.07%.
Voltage drop at the ampacity gauge2 × 12.9 × I × L / CM3.9510 V.
Voltage drop % at the ampacity gaugeVD ÷ V × 1003.29%.
Distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V3% × V × CM ÷ (2 × 12.9 × I)45.5581 ft → 45.56 ft.
Current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V3% × V × CM ÷ (2 × 12.9 × L)28.9674 A → 28.97 A.
Distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V3% × V × CM ÷ (2 × 12.9 × I)38.2326 ft → 38.23 ft.
Current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V3% × V × CM ÷ (2 × 12.9 × L)23.0372 A → 23.04 A.
Distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V3% × V × CM ÷ (2 × 12.9 × I)91.1163 ft → 91.12 ft.
Distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V3% × V × CM ÷ (2 × 12.9 × I)48.2791 ft → 48.28 ft.
Load 15 Asame modelAmp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47%.
Load 30 Asame modelAmp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95%.
Distance 100 ftsame modelAmp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60%.
Voltage 240 Vsame modelAmp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65%.
Load 100 Asame modelAmp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28%.
Max drop 5%same modelAmp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29%.

Who uses this

  • The homeowner running a 20-amp circuit 50 feet: they learn the wire is 10 AWG, not 12 AWG — and they check the 100-foot branch (8 AWG) before they run the cable twice as far.
  • The electrician sizing a 240 V subpanel feed: they learn the drop gauge is 14 AWG at 240 V — and they check the 100-amp branch (1 AWG) to see ampacity take over at big loads.
  • The DIYer adding a 15-amp outlet: they learn 14 AWG fails on drop at 3.92% — and they check the 30-amp branch (8 AWG) to see the same pattern at higher current.
  • The planner choosing a drop limit: they learn 12 AWG passes at a 5% limit — and they check the 3% table (45.56 ft for 12 AWG) to see how far the stricter limit reaches.

Accuracy & limitations

The math is first-principles electrical: VD = 2 × 12.9 × I × L / CM; VD% = VD / V × 100; Lmax = 3.6 × CM / 516 at 20 A / 120 V / 3%; recommended = larger wire of amp gauge and drop gauge. The ampacities are NEC Table 310.16, 60°C column, copper — the conservative column used for NM-cable terminations. The 4-decimal exact is shown where the rounding matters: the distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V is 45.5581 ft (shown as 45.56 ft); at 45.55 ft the drop is 2.9995%, at 45.56 ft it is 3.0001%, at 45.57 ft it is 3.0008%. The current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V is 28.9674 A (shown as 28.97 A); at 28.96 A the drop is 2.9992%, at 28.97 A it is 3.0003%. What the model cannot do is replace a licensed electrician: it does not model derating for bundled cables, high ambient temperature, aluminum wire, or local code amendments — and the 3% limit is an informational recommendation, not a code requirement. For the wire gauge chart itself, see the wire gauge chart; for another construction reference table, see the dryer vent length chart and the concrete mix chart. This is a calculator, not an electrical opinion.

Cite this calculatorBright Side Kit. “Electrical Wire Size Chart: Ampacity & Voltage Drop 2026” brightoolbox.com, 2026. Method: ampacity from NEC Table 310.16, 60°C column, copper conductors — the conservative column used for NM-cable terminations. Voltage drop (single-phase copper, K = 12.9): VD = 2 × 12.9 × I × L / CM; VD% = VD / V × 100. Recommended gauge = the larger wire of (a) the smallest gauge whose ampacity ≥ load, and (b) the smallest gauge whose VD% ≤ max drop. The 3% limit is the NEC informational recommendation (FPN), not a code requirement; 14 AWG is the smallest gauge in the table; aluminum needs larger wire (not covered); always check local code and get a licensed electrician for service work. Table (max one-way distance at 20 A / 120 V / 3% drop — every cell derived from Lmax = 3.6 × CM / 516): 14 AWG → 15 A / 4,110 CM / 28.67 ft; 12 AWG → 20 A / 6,530 CM / 45.56 ft; 10 AWG → 30 A / 10,380 CM / 72.42 ft; 8 AWG → 40 A / 16,510 CM / 115.19 ft; 6 AWG → 55 A / 26,240 CM / 183.07 ft; 4 AWG → 70 A / 41,740 CM / 291.21 ft; 3 AWG → 85 A / 52,620 CM / 367.12 ft; 2 AWG → 95 A / 66,360 CM / 462.98 ft; 1 AWG → 110 A / 83,690 CM / 583.88 ft; 1/0 AWG → 125 A / 105,600 CM / 736.74 ft; 2/0 AWG → 145 A / 133,100 CM / 928.60 ft; 3/0 AWG → 165 A / 167,800 CM / 1,170.70 ft; 4/0 AWG → 195 A / 211,600 CM / 1,476.28 ft. Defaults: load 20 A, distance 50 ft, 120 V, max drop 3% → ampacity gauge 12 AWG, drop gauge 10 AWG, recommended 10 AWG; VD at 12 AWG 3.9510 V / 3.29% (over 3%, so 12 AWG fails on drop); VD at 10 AWG 2.4855 V / 2.07%. Branches: Load 15 A → Amp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47% (VD at 14 AWG 3.92% fails drop; 12 AWG 2.47% passes); Load 30 A → Amp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95% (VD at 10 AWG 3.11% fails drop; 8 AWG 1.95% passes); Distance 100 ft → Amp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60% (VD at 12 AWG 6.58%, 10 AWG 4.14%, 8 AWG 2.60%); Voltage 240 V → Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65% (drop passes on 14 AWG at 240 V, but ampacity still requires 12 AWG — the drop gauge is SMALLER than the ampacity gauge here); Load 100 A → Amp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28% (drop passes on 4 AWG, ampacity requires 1 AWG); Max drop 5% → Amp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29% (12 AWG passes at the 5% limit). Reverses: distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V = 45.56 ft (exact 45.5581 ft; at 45.55 ft the drop is 2.9995%, at 45.56 ft it is 3.0001%, at 45.57 ft it is 3.0008%); current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V = 28.97 A (exact 28.9674 A; at 28.96 A the drop is 2.9992%, at 28.97 A it is 3.0003%); distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V = 38.23 ft (exact 38.2326 ft; at 38.23 ft the drop is 2.9998%, at 38.24 ft it is 3.0006%); current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V = 23.04 A (exact 23.0372 A; at 23.03 A the drop is 2.9991%, at 23.04 A it is 3.0004%); distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V = 91.12 ft (exact 91.1163 ft; at 91.11 ft the drop is 2.9998%, at 91.12 ft it is 3.0001%); distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V = 48.28 ft (exact 48.2791 ft; at 48.27 ft the drop is 2.9994%, at 48.28 ft it is 3.0001%). Edges: 0 A load → Amp 14 AWG, drop 14 AWG, recommended 14 AWG, VD 0.00%; 0 ft distance → Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 0.00%; 200 A load → Amp none, drop 1 AWG, recommended none, VD — (VD at 4/0 is only 1.02% — drop is fine, ampacity is the binding limit). Bright Side Kit. "Electrical Wire Size Chart: Ampacity & Voltage Drop 2026" https://brightoolbox.com/electrical-wire-size-chart/ Accessed October 25, 2026.
Embed this calculator

Paste this into any web page to embed the live calculator. The “Powered by Bright Side Kit” link below it must stay intact.

Frequently asked questions

What size wire do I need for a 20-amp circuit 50 feet away?

10 AWG. A 20-amp load 50 feet away needs 10 AWG, not 12 AWG — 12 AWG carries the current, but its voltage drop is 3.29%, over the 3% limit. At 10 AWG the drop is 2.07%.

How far can I run 12 AWG on a 20-amp circuit?

45.56 ft. At 20 A / 120 V / 3% drop, 12 AWG reaches 45.56 ft — the distance for exactly 3.00% drop is 45.56 ft (exact 45.5581 ft). At 45.57 ft the drop is already 3.0008%.

Is the 3% voltage drop limit a code requirement?

No — it is an NEC informational recommendation (FPN), not a code requirement. The code does not enforce 3%, but lights dim and motors run hot when the drop is much bigger, so 3% is the standard design target.

Why does 240 V let me use smaller wire?

Because the drop halves. At 240 V the same 20-amp load 50 feet away drops only 1.65% on 12 AWG — and the drop gauge falls to 14 AWG, smaller than the ampacity gauge. The recommendation stays 12 AWG, the larger wire.

What size wire for a 100-amp load?

1 AWG. A 100-amp load needs 1 AWG by ampacity — the drop passes on 4 AWG, but ampacity requires 1 AWG. At 1 AWG the drop is 1.28%.

What size wire for a 200-amp service?

No single gauge in this table. 4/0 AWG maxes at 195 A, so a 200-amp load has no ampacity gauge — parallel runs or larger service wire are needed. The voltage drop at 4/0 is only {num(d["edgeI200Vd40Pct"])}%, so drop is not the problem.

How far can I run 14 AWG on a 15-amp circuit?

28.67 ft. At 20 A / 120 V / 3% drop, 14 AWG reaches 28.67 ft. On a 15-amp load the distance for exactly 3.00% drop is 38.23 ft (exact 38.2326 ft).

What is the smallest wire size in the table?

14 AWG. 14 AWG is the smallest gauge in the table — it carries 15 A and has 4,110 circular mils. Smaller gauges exist, but they are not used for branch circuits.