Electrical wire size chart
What size wire do you need? Enter the load current, the one-way distance and the voltage to find the minimum gauge by ampacity and voltage drop, with the full NEC copper table.
★ CONSTRUCTION · WIRE SIZE · REFERENCE TABLE #246
Recommended 10 AWG — ampacity needs 12 AWG, voltage drop needs 10 AWG. A 20-amp load 50 feet away needs 10 AWG, not 12 — 12 AWG carries the current fine, but its voltage drop is 3.29%, over the 3% limit. Enter your load, distance and voltage to find your gauge.
What size wire do you need? Enter the load current, the one-way distance and the voltage to find the minimum gauge by ampacity and voltage drop, with the full NEC copper table.
Two limits decide a wire’s size, and they are not the same. Ampacity is how much current the wire can carry without overheating — 12 AWG carries 20 A. Voltage drop is how much voltage the wire itself eats on the way there and back — and on a long run it is the binding limit. On the defaults — load 20 A, distance 50 ft, voltage 120 V, max drop 3% — the ampacity gauge is 12 AWG, the drop gauge is 10 AWG, the recommended gauge is 10 AWG, the voltage drop at the recommended gauge is 2.4855 V / 2.07% and the voltage drop at the ampacity gauge is 3.9510 V / 3.29% — over 3%, so 12 AWG fails on drop.
| Gauge | Ampacity | Circular mils | Max distance at 20 A / 120 V / 3% |
|---|---|---|---|
| 14 AWG | 15 A | 4,110 | 28.67 ft |
| 12 AWG | 20 A | 6,530 | 45.56 ft |
| 10 AWG | 30 A | 10,380 | 72.42 ft |
| 8 AWG | 40 A | 16,510 | 115.19 ft |
| 6 AWG | 55 A | 26,240 | 183.07 ft |
| 4 AWG | 70 A | 41,740 | 291.21 ft |
| 3 AWG | 85 A | 52,620 | 367.12 ft |
| 2 AWG | 95 A | 66,360 | 462.98 ft |
| 1 AWG | 110 A | 83,690 | 583.88 ft |
| 1/0 AWG | 125 A | 105,600 | 736.74 ft |
| 2/0 AWG | 145 A | 133,100 | 928.60 ft |
| 3/0 AWG | 165 A | 167,800 | 1,170.70 ft |
| 4/0 AWG | 195 A | 211,600 | 1,476.28 ft |
At the defaults — load 20 A, distance 50 ft, voltage 120 V, max drop 3% — the ampacity gauge is 12 AWG, the drop gauge is 10 AWG, the recommended gauge is 10 AWG, the voltage drop at the recommended gauge is 2.4855 V / 2.07% and the voltage drop at the ampacity gauge is 3.9510 V / 3.29%. Check the identities: VD = 2 × 12.9 × I × L / CM; VD% = VD / V × 100; Lmax = 3.6 × CM / 516 at 20 A / 120 V / 3%; recommended = larger wire of amp gauge and drop gauge. Rounding convention: totals are computed from unrounded values, so rounded parts may differ by a cent from their rounded sum.
| Scenario | Ampacity | Drop | Recommended | VD% at recommended |
|---|---|---|---|---|
| Default (20 A, 50 ft, 120 V, 3%) | 12 AWG | 10 AWG | 10 AWG | 2.07% |
| Load 15 A | 14 AWG | 12 AWG | 12 AWG | 2.47% |
| Load 30 A | 10 AWG | 8 AWG | 8 AWG | 1.95% |
| Distance 100 ft | 12 AWG | 8 AWG | 8 AWG | 2.60% |
| Voltage 240 V | 12 AWG | 14 AWG | 12 AWG | 1.65% |
| Load 100 A | 1 AWG | 4 AWG | 1 AWG | 1.28% |
| Max drop 5% | 12 AWG | 12 AWG | 12 AWG | 3.29% |
Setup: load 20 A, distance 50 ft, voltage 120 V, max drop 3%.
Line 1 — the ampacity gauge. 12 AWG carries 20 A, so the ampacity gauge is 12 AWG.
Line 2 — the voltage drop on 12 AWG. VD = 2 × 12.9 × 20 × 50 / 6,530 = 3.9510 V. As a percentage: 3.9510 / 120 × 100 = 3.29% — over the 3% limit, so 12 AWG fails on drop.
Line 3 — the drop gauge. The next size up, 10 AWG, has 10,380 circular mils: VD = 2 × 12.9 × 20 × 50 / 10,380 = 2.4855 V, which is 2.07% — inside the limit, so the drop gauge is 10 AWG.
Line 4 — the recommendation. The recommended gauge is the larger wire of the two — 10 AWG. The 3% limit is the NEC informational recommendation, not a code requirement.
Reverse: the distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V is 45.56 ft (exact 45.5581 ft); at 45.55 ft the drop is 2.9995%, at 45.56 ft it is 3.0001%, at 45.57 ft it is 3.0008%. The current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V is 28.97 A (exact 28.9674 A); at 28.96 A the drop is 2.9992%, at 28.97 A it is 3.0003%. The distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V is 38.23 ft (exact 38.2326 ft); at 38.23 ft the drop is 2.9998%, at 38.24 ft it is 3.0006%. The current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V is 23.04 A (exact 23.0372 A); at 23.03 A the drop is 2.9991%, at 23.04 A it is 3.0004%. The distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V is 91.12 ft (exact 91.1163 ft); at 91.11 ft the drop is 2.9998%, at 91.12 ft it is 3.0001%. The distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V is 48.28 ft (exact 48.2791 ft); at 48.27 ft the drop is 2.9994%, at 48.28 ft it is 3.0001%.
Load 15 A: Amp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47%. 14 AWG carries 15 A, but its drop is 3.92% — over the limit — so the drop gauge is 12 AWG at 2.47%.
Load 30 A: Amp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95%. 10 AWG carries 30 A, but its drop is 3.11% — over the limit — so the drop gauge is 8 AWG at 1.95%.
Distance 100 ft: Amp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60%. Doubling the distance doubles the drop: 12 AWG is 6.58%, 10 AWG is 4.14%, and only 8 AWG at 2.60% passes.
Voltage 240 V: Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65%. At 240 V the drop halves, so the drop gauge is 14 AWG — SMALLER than the ampacity gauge — and the recommendation stays 12 AWG, the larger wire.
Load 100 A: Amp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28%. The drop passes on 4 AWG, but ampacity requires 1 AWG — the drop gauge is smaller than the ampacity gauge again, and the recommendation is the larger wire, 1 AWG.
Max drop 5%: Amp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29%. At a 5% limit 12 AWG passes with a 3.29% drop, so the ampacity and drop gauges agree at 12 AWG.
The model assumes single-phase copper conductors, K = 12.9, the NEC Table 310.16 60°C column, and a one-way distance — the wire runs there and back, so the voltage drop counts both ways. It assumes the load is continuous at the current you enter and the temperature is within the 60°C column’s range — it does not model derating for bundled cables, high ambient temperature, or aluminum wire, which needs larger gauges. With a 0 A load the ampacity gauge is 14 AWG, the recommended gauge is 14 AWG and the voltage drop is 0.00% — no load, no drop. With a 0 ft distance the recommended gauge is 12 AWG and the voltage drop is 0.00%. With a 200 A load the ampacity gauge is none — 4/0 AWG maxes at 195 A, so no single copper gauge in the table carries 200 A (parallel runs or larger service wire needed); the voltage drop at 4/0 is only 1.02% — drop is fine, ampacity is the binding limit. Rounding convention: totals are computed from unrounded values, so rounded parts may differ by a cent from their rounded sum; the reverses are nearest-value solutions, and the exact unrounded figures (45.5581, 28.9674, 38.2326, 23.0372, 91.1163, 48.2791) are stated wherever the rounded figures appear.
| Output | Formula | What it means |
|---|---|---|
| Ampacity gauge | the smallest gauge whose ampacity ≥ load | 12 AWG. |
| Drop gauge | the smallest gauge whose VD% ≤ max drop | 10 AWG. |
| Recommended gauge | the larger wire of the ampacity gauge and the drop gauge | 10 AWG. |
| Voltage drop at the recommended gauge | 2 × 12.9 × I × L / CM, then ÷ V × 100 | 2.4855 V. |
| Voltage drop % at the recommended gauge | VD ÷ V × 100 | 2.07%. |
| Voltage drop at the ampacity gauge | 2 × 12.9 × I × L / CM | 3.9510 V. |
| Voltage drop % at the ampacity gauge | VD ÷ V × 100 | 3.29%. |
| Distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V | 3% × V × CM ÷ (2 × 12.9 × I) | 45.5581 ft → 45.56 ft. |
| Current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V | 3% × V × CM ÷ (2 × 12.9 × L) | 28.9674 A → 28.97 A. |
| Distance for exactly 3.00% drop at 14 AWG / 15 A / 120 V | 3% × V × CM ÷ (2 × 12.9 × I) | 38.2326 ft → 38.23 ft. |
| Current for exactly 3.00% drop at 8 AWG / 100 ft / 120 V | 3% × V × CM ÷ (2 × 12.9 × L) | 23.0372 A → 23.04 A. |
| Distance for exactly 3.00% drop at 12 AWG / 20 A / 240 V | 3% × V × CM ÷ (2 × 12.9 × I) | 91.1163 ft → 91.12 ft. |
| Distance for exactly 3.00% drop at 10 AWG / 30 A / 120 V | 3% × V × CM ÷ (2 × 12.9 × I) | 48.2791 ft → 48.28 ft. |
| Load 15 A | same model | Amp 14 AWG, drop 12 AWG, recommended 12 AWG, VD 2.47%. |
| Load 30 A | same model | Amp 10 AWG, drop 8 AWG, recommended 8 AWG, VD 1.95%. |
| Distance 100 ft | same model | Amp 12 AWG, drop 8 AWG, recommended 8 AWG, VD 2.60%. |
| Voltage 240 V | same model | Amp 12 AWG, drop 14 AWG, recommended 12 AWG, VD 1.65%. |
| Load 100 A | same model | Amp 1 AWG, drop 4 AWG, recommended 1 AWG, VD 1.28%. |
| Max drop 5% | same model | Amp 12 AWG, drop 12 AWG, recommended 12 AWG, VD 3.29%. |
The math is first-principles electrical: VD = 2 × 12.9 × I × L / CM; VD% = VD / V × 100; Lmax = 3.6 × CM / 516 at 20 A / 120 V / 3%; recommended = larger wire of amp gauge and drop gauge. The ampacities are NEC Table 310.16, 60°C column, copper — the conservative column used for NM-cable terminations. The 4-decimal exact is shown where the rounding matters: the distance for exactly 3.00% drop at 12 AWG / 20 A / 120 V is 45.5581 ft (shown as 45.56 ft); at 45.55 ft the drop is 2.9995%, at 45.56 ft it is 3.0001%, at 45.57 ft it is 3.0008%. The current for exactly 3.00% drop at 10 AWG / 50 ft / 120 V is 28.9674 A (shown as 28.97 A); at 28.96 A the drop is 2.9992%, at 28.97 A it is 3.0003%. What the model cannot do is replace a licensed electrician: it does not model derating for bundled cables, high ambient temperature, aluminum wire, or local code amendments — and the 3% limit is an informational recommendation, not a code requirement. For the wire gauge chart itself, see the wire gauge chart; for another construction reference table, see the dryer vent length chart and the concrete mix chart. This is a calculator, not an electrical opinion.
Bright Side Kit. "Electrical Wire Size Chart: Ampacity & Voltage Drop 2026" https://brightoolbox.com/electrical-wire-size-chart/ Accessed October 25, 2026.10 AWG. A 20-amp load 50 feet away needs 10 AWG, not 12 AWG — 12 AWG carries the current, but its voltage drop is 3.29%, over the 3% limit. At 10 AWG the drop is 2.07%.
45.56 ft. At 20 A / 120 V / 3% drop, 12 AWG reaches 45.56 ft — the distance for exactly 3.00% drop is 45.56 ft (exact 45.5581 ft). At 45.57 ft the drop is already 3.0008%.
No — it is an NEC informational recommendation (FPN), not a code requirement. The code does not enforce 3%, but lights dim and motors run hot when the drop is much bigger, so 3% is the standard design target.
Because the drop halves. At 240 V the same 20-amp load 50 feet away drops only 1.65% on 12 AWG — and the drop gauge falls to 14 AWG, smaller than the ampacity gauge. The recommendation stays 12 AWG, the larger wire.
1 AWG. A 100-amp load needs 1 AWG by ampacity — the drop passes on 4 AWG, but ampacity requires 1 AWG. At 1 AWG the drop is 1.28%.
No single gauge in this table. 4/0 AWG maxes at 195 A, so a 200-amp load has no ampacity gauge — parallel runs or larger service wire are needed. The voltage drop at 4/0 is only {num(d["edgeI200Vd40Pct"])}%, so drop is not the problem.
28.67 ft. At 20 A / 120 V / 3% drop, 14 AWG reaches 28.67 ft. On a 15-amp load the distance for exactly 3.00% drop is 38.23 ft (exact 38.2326 ft).
14 AWG. 14 AWG is the smallest gauge in the table — it carries 15 A and has 4,110 circular mils. Smaller gauges exist, but they are not used for branch circuits.