The model, stated exactly
Thickness in inches = R-value ÷ R per inch. R-values add: existing R plus added R equals total R. The per-inch figures used here are the standard nominal values for each material: fiberglass batts R-3.2, blown cellulose R-3.5, mineral wool batts R-3.3, open-cell spray foam R-3.6, closed-cell spray foam R-6.5, and rigid XPS foam R-5.0. Every cell in the chart below is that division, rounded to one decimal place.
Thickness needed, in inches, by target R-value
| Material | R/in | R-13 | R-19 | R-30 | R-38 | R-49 | R-60 |
| Fiberglass batts | 3.2 | 4.1 | 5.9 | 9.4 | 11.9 | 15.3 | 18.8 |
| Blown cellulose | 3.5 | 3.7 | 5.4 | 8.6 | 10.9 | 14.0 | 17.1 |
| Mineral wool batts | 3.3 | 3.9 | 5.8 | 9.1 | 11.5 | 14.8 | 18.2 |
| Open-cell spray foam | 3.6 | 3.6 | 5.3 | 8.3 | 10.6 | 13.6 | 16.7 |
| Closed-cell spray foam | 6.5 | 2.0 | 2.9 | 4.6 | 5.8 | 7.5 | 9.2 |
| Rigid XPS foam | 5.0 | 2.6 | 3.8 | 6.0 | 7.6 | 9.8 | 12.0 |
Attic targets by climate zone (DOE-style ranges)
| Climate zone | Attic target | What it means in practice |
| Zones 1–2 (hot: South Florida, South Texas, Hawaii) | R30–R49 | Heat defence first; the lower end suits mild winters, the upper end suits year-round cooling loads. |
| Zone 3 (warm: Atlanta, Dallas, Los Angeles) | R30–R60 | Balanced heating and cooling; most existing attics here sit well below target and gain the most from topping up. |
| Zone 4 (mixed: Washington DC, St. Louis, Seattle) | R38–R60 | Real winters arrive, so the floor rises to R-38; aim mid-range unless the attic is easy to fill. |
| Zones 5–8 (cold to very cold: Chicago, Minneapolis, Alaska) | R49–R60 | Deep insulation pays fastest here; R-49 is the floor, not the aspiration, in the coldest zones. |
Walls and floors, briefly. Cavity walls typically target R-13 to R-21 depending on zone and stud depth, and floors over unconditioned space target roughly R-13 in warm zones rising to R-30 in cold ones. Walls are depth-limited by the studs, which is why high-R-per-inch materials matter there; attics have room to stack, so cheaper per-inch materials win. Always check your local energy code, which can exceed these general ranges.
The worked example, line by line
Setup: existing R-11, target R-49, fiberglass batts at R-3.2 per inch.
Line 1 — added R. 49 − 11 = R-38.
Line 2 — thickness. 38 ÷ 3.2 = 11.875, rounded to 11.9 in.
Try these
Target R-60. From R-11 to R-60 you must add R-49, which is 49 ÷ 3.2 = 15.3 in of fiberglass batts.
Cellulose instead. The same R-38 gap in blown cellulose is 38 ÷ 3.5 = 10.9 in — a full inch thinner than fiberglass for the same insulation.
Starting from R-30. From R-30 to R-49 you must add R-19, which is 19 ÷ 3.2 = 5.9 in of fiberglass batts.
Output · formula · meaning
| Output | Formula | What it means |
| Added R | Target R − current R | R-38 at the defaults — the insulation gap you must close. |
| Thickness to add | Added R ÷ R per inch | 11.9 in of fiberglass batts at the defaults — how deep to fill. |
| Chart reading | Target R ÷ R per inch | Read any material across to any target: R-49 in closed-cell foam is only 7.5 in, against 15.3 in of fiberglass. |
Who uses this
- The homeowner topping up an attic: measures the existing depth, converts it to R, and reads off how many more inches of blown cellulose to order.
- The remodeler choosing a wall assembly: compares fiberglass against closed-cell foam where stud depth caps the thickness, and picks the material that reaches the target within the cavity.
- The DIYer pricing a job: turns the thickness into bags or boards from the product coverage, using the area shown in the calculator for context.
- The buyer checking a new home: looks up the zone target, asks what the attic actually holds, and prices the shortfall before making an offer.
Accuracy & limitations
The division is exact for the nominal per-inch values shown, but real products vary: batts compress, blown insulation settles, and gaps, framing, and air leaks cut effective R below the labelled total. Treat the chart as a planning figure and round thickness up, never down. Zone targets are DOE-style general ranges, not a substitute for your local building or energy code. Error policy: empty, non-numeric, or negative inputs, a zero area, and a target at or below the current R are reported as errors rather than computed.
Cite this calculatorBright Side Kit. “Insulation R-Value Chart & Calculator — Bright Side Kit.” brightoolbox.com, 2026.Bright Side Kit. "Insulation R-Value Chart & Calculator." https://brightoolbox.com/insulation-r-value-chart/ Accessed October 24, 2026.